CONTINUOUS CURRENT RATING OF AC HIGH VOLTAGE CIRCUIT BREAKER


The rated continuous current of a circuit breaker is the designated limit of current in rms amperes at rated frequency which it shall be required to carry continuously without exceeding any of the limitations designated . For rated continuous currents, refer to the tables of preferred ratings in ANSI C37.06-1979.

Conditions of Continuous Current Rating.
The conditions on which continuous current ratings are based are as follows:

1) Breakers are used under the usual service conditions.

2) Current ratings shall be based on the total temperature limits of the materials used for breaker parts. A temperature rise reference is given to permit testing at reduced ambient.

3) Breakers designed for installation in enclosures shall have their ratings based on the ventilation of such enclosures and a 40°C ambient temperature outside the enclosure.

4) Outdoor breakers and indoor breakers without enclosures shall have ratings based on a 40°C ambient temperature.

Temperature Limitations.
Limitations on Insulating Material.
The temperature of materials used to insulate the main power circuit conducting parts from phase to ground, from phase to phase, or from terminal to terminal of an open breaker shall be limited to the values listed in columns B and C in Table 2.

It is recognized that these limits are generally less than those associated with the insulating class in IEEE Std 1-1969, General Principles for Temperature Limits in the Rating of Electric Equipment, since such insulation may be subject to severe mechanical as well as dielectric stress when used in high-voltage circuit breakers.

Where outdoor apparatus bushings within the scope of ANSI/IEEE Std 21-1976, General Requirements and Test Procedures for Outdoor Apparatus Bushings, and ANSI/IEEE Std 24-1977, Standard Electrical, Dimensional, and Related Requirements for Outdoor Apparatus Bushings, are used, the temperature limits in Table 3 do not apply to the bushings.

Limitations on Main Contacts.
The temperature of the main contacts used in circuit breakers shall not exceed the values listed in Table 3. Contacts in other than oil or air may be operated at other temperatures providing it can be shown, by experience or tests acceptable to the user, that accelerated deterioration will not occur. (Future consideration will be given to standardized values.)

Conducting Joints Other than Terminals for Insulated Cable Connection.
The temperature of conducting joints in the main power circuit of a circuit breaker shall not exceed the values listed in Table 4. Conducting joints in other than oil or air may be operated at other temperatures providing it can be shown, by experience or tests acceptable to the user, that accelerated deterioration will not occur. (Future consideration will be given to standardized values.)

Terminals for Connection to Insulated Cable.
Terminals of circuit breakers designed for direct cable connection shall not exceed 45°C rise or 85°C hottest spot total temperature when connected to 85°C maximum insulated cable, rated for the full continuous current rating of the circuit breaker.

Limitations for Parts Subject to Contact by Personnel.
Circuit breaker parts handled by the operator in the normal course of his duties shall have no higher total temperature than 50°C. Circuit breakers having external surfaces accessible to an operator in the normal course of his duties shall have no higher total temperature on the surfaces than 70°C. Circuit breakers having external surfaces not accessible to an operator in the normal course of his duties shall have no higher total temperature on the surfaces than 110°C.

Limitations on Other Materials.
Other materials shall be chosen so that the maximum temperatures to which they may be subjected shall not cause accelerated deterioration.

No comments:

Post a Comment