TRANSFORMER PHASE TIME OVERCURRENT RELAY PROTECTION
Time overcurrent relays are inexpensive, simple, and reliable protective devices. Since sensitive settings and fast operation are usually not possible with overcurrent relays, they will provide limited protection for internal transformer faults.
Since the pickup value of phase overcurrent relays must be high enough to take advantage of the overload capabilities of the transformer and be capable of withstanding energizing inrush currents, insensitive settings result.
Fast operation is not possible, since the transformer relays should coordinate with load-side protection, including dealing with reclosing cycles and service restoration inrush. Where time overcurrent relays are used for primary transformer protection, extensive damage to the transformer from an internal fault may occur.
Settings of phase overcurrent relays on transformers involve a compromise between the requirements of operation and protection. The pickup setting should be high enough to permit overloading the transformer when necessary, but the higher the setting, the less the protection.
A setting of 125–150% of maximum kVA nameplate rating of a transformer is common, although higher values are sometimes used. On multiplerated transformers, a higher setting may be necessary so as to utilize the full capability of the transformer at the higher forced-cooling rating.
If overcurrent protection (relays or fuses) is applied only to the high-voltage (Δ) side of a Δ−Y grounded transformer, it can have a problem providing sensitive fault protection for the transformer and still coordinating with low-side protective devices. For low-voltage (Y side) phase-to-phase faults, the high-side line current will be 115% of the low-voltage per unit fault current.
For low-voltage (Y side) phase-to-ground faults, the high-side line current will be only 58% of the low voltage per unit fault current. When the Y is grounded through a resistor, the high-side fault current may be less than the maximum transformer load current.
Similar concerns are applicable when the Y is grounded through a reactor. The time setting should coordinate with relays on downstream equipment. Transformers are mechanically and thermally limited in their ability to withstand short-circuit current for finite periods of time.
For proper backup protection, the relays should operate before the transformer is damaged by an external fault. A for the transformer through-fault current duration limits and relay setting examples.) Solid-state or microprocessor-based relays with special features such as fast reset should be evaluated for coordination with downstream devices.
In setting transformer overcurrent relays, the short-time overload capability of the transformer in question should not be exceeded. Low values of 3.5 or less times normal base current may result from overloading rather than faults. For such cases see IEEE C57.91-1995, since allowable time duration may be different from those in the through-fault current duration curves. Pending establishment of additional transformer standards, it is recommended that the manufacturer be consulted for the capability of a specific transformer.
Distribution supply transformers are subject to many through-faults and autoreclosing into line faults. The use of extremely inverse tripping characteristics for distribution circuit reclosers permits fast clearing of the more severe faults.
Where the use of instantaneous relaying for either transformer or distribution feeder protection is limited, time overcurrent relays with very inverse time characteristics will provide fast clearing for the more severe faults.
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment